Header Ads

ITEM 714 – WATER


714.1 Description

This Item covers criteria for acceptance of Questionable Water either natural or wash water for use in concrete.

714.2 Requirements

The mixing water shall be clear and apparently clean. If it contains quantities or substances that discolor it or make it smell or taste unusual or objectionable, or cause suspicion, it shall not be used unless service records of concrete made with it (or other information) indicated that it is not injurious to the quality, shall be subject to the acceptance criteria as shown in Table 714.1 and Table 714.2 or as designated by the purchaser.
When wash water is permitted, the producer will provide satisfactory proof or data of non-detrimental effects if potentially reactive aggregates are to be used. Use of wash water will be discontinued if undesirable reactions with admixtures or aggregates occur.

Table714.1 – Acceptance Criteria For Questionable Water Supplies
Physical Properties
Limits
Compressive strength, min. %
Control at 7 days
Time of Setting deviation from control
Time of Setting (Gillmore Test)
   Initial
   Final
Appearance
Color
Odor
Total Solids
pH Value

90
From 1:100 earlier to 1:30 later

No marked change
No marked change
Clear
Colorless
Odorless
500 parts/million max.
4.5 to 8.5


 Table714.2 Chemical Limitation for Wash Water
Chemical Properties
Limits
Chemical Requirements, Minimum Concentration
Chloride as C1(-1) expressed as a mass percent of cement when added to the C1 (-1) in the other components of the concrete mixtures shall not exceed the following levels:
1. Prestressed Concrete
2. Conventionally reinforced concrete in a moist environment and exposed to chloride
3. Conventionally reinforced concrete in a moist environment but not exposed to chloride
4. Above ground building construction where the concrete will stay dry
Sulfate as SO4, ppmA
Alkalies as (Na2O + 0.658 K2O), ppm
Total Solids, ppm








0.06 percent
0.10 percent


0.15 percent


No limit for corrosion

3000
600
50000

A          Wash water reused as mixing water in concrete may exceed the listed concentrations of sulfate if it can be shown that the concentration calculated in the total mixing water, including mixing water on the aggregate and other sources, does not exceed that stated limits.

Water will be tested in accordance with, and shall meet the suggested requirements of AASHTO T 26.


Water known to be of potable quality may be used without test.

No comments

Powered by Blogger.